Energetic and exergetic approach to vapor compression refrigeration cycle with two-stage and intercooler for new refrigerants


DİKMEN E., ŞENCAN ŞAHİN A., SELBAŞ R.

Energy Education Science and Technology Part A: Energy Science and Research, cilt.26, sa.2, ss.205-219, 2011 (Scopus) identifier

  • Yayın Türü: Makale / Tam Makale
  • Cilt numarası: 26 Sayı: 2
  • Basım Tarihi: 2011
  • Dergi Adı: Energy Education Science and Technology Part A: Energy Science and Research
  • Derginin Tarandığı İndeksler: Scopus
  • Sayfa Sayıları: ss.205-219
  • Anahtar Kelimeler: COP, Exergy analysis, Refrigeration system, Two-stage, Vapor compression refrigeration
  • Isparta Uygulamalı Bilimler Üniversitesi Adresli: Hayır

Özet

In this study, first and second law analysis of vapor compression refrigeration cycle with two-stage and intercooler using refrigerants R134a, R404a, R407c, R410a, R507 which do not damage to ozone layer is carried out. The coefficient of performance (COP), exergetic efficiency (η ex) and total irreversibility rate of the system in the different operating conditions for these refrigerants has been investigated. COP, exergetic efficiency and total irreversibility rate comparisons between refrigerants were performed. The results indicate that COP and exergetic efficiency of refrigeration system with two-stage using R134a is better than system using other refrigerants. The irreversibility rate in the system using R507 is highest. © Sila Science.