Enhanced exergy analysis of a waste heat powered ejector refrigeration system for different working fluids


Ustaoglu A., ALPTEKİN M., Akay M. E., SELBAŞ R.

International Journal of Exergy, vol.24, no.2-4, pp.301-324, 2017 (SCI-Expanded, Scopus)

  • Publication Type: Article / Article
  • Volume: 24 Issue: 2-4
  • Publication Date: 2017
  • Doi Number: 10.1504/ijex.2017.087698
  • Journal Name: International Journal of Exergy
  • Journal Indexes: Science Citation Index Expanded (SCI-EXPANDED), Scopus
  • Page Numbers: pp.301-324
  • Keywords: Advanced exergy analysis, Conventional exergy analysis, Dry fluid, Ejector refrigeration, Enhanced exergy analysis, Isentropic fluid, Rotary kiln, Waste heat, Wet fluids
  • Isparta University of Applied Sciences Affiliated: No

Abstract

Conventional and enhanced exergy analyses of a waste heat powered ejector refrigeration system using exhausted gas from rotary kiln were carried out. Isentropic (R290, R141b and R142b), wet (R134a and R152a) and dry fluids (R600a) were considered in the cycle in terms of avoidable-unavoidable parts of the exergy destruction to decide improvement potentials of the overall system. The results indicate a significant issue; the importance of component can change regarding refrigerant. The ejector comes into view as an important component to improve the overall cycle performance for R134a while the generator shows the best improvement potential for R600a.